The MS116-0.16 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 0.16 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
SKU: 1SAM250000R1001
Categories: Motor Starters
Rated Insulation Voltage (Ui) | 690 volt |
Ambient Air Temperature | Around the Enclosure 0 ... +40 degree Celsius, Operation -25 ... +70 degree Celsius, Operation Compensated -25 ... +55 degree Celsius, Storage -50 ... +80 degree Celsius |
Full Load Amps Motor Use | (110 ... 120 V AC) Three Phase 0.96 ampere, (200 V AC) Three Phase 0.16 ampere, (208 V AC) Three Phase 0.16 ampere, (220 ... 240 V AC) Three Phase 0.16 ampere, (440 ... 480 V AC) Three Phase 0.16 ampere, (550 ... 600 V AC) Three Phase 0.16 ampere |
General Use Rating UL/CSA | (600 V AC) 0.16 ampere |
Rated Frequency (f) | Main Circuit 50 hertz/Main Circuit 60 hertz |
Rated Current (In) | 0.16A |
Rated Operational Voltage | Main Circuit 690 volt AC |
Terminal Type | Screw Terminals |
Number Of Poles | 3 |
Package Gross Weight | 0.24 kilogram |
Product Range | MO-MS |
Invoice Description | MS116-0.16 Manual Motor Starter Trip class 10A, 0.1 ... 0.16A |
Package Height | 50 millimetre |
Package Length | 95 millimetre |
Package Width | 92 millimetre |
Max Operating Voltage UL/CSA | Main Circuit 600 volt AC |
Extended Product Type | MS116-0.16 |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 50 kiloampere, (400 V AC) 50 kiloampere, (440 V AC) 50 kiloampere, (500 V AC) 30 kiloampere, (690 V AC) 30 kiloampere |
Rated Operational Current (Ie) | 0.16A |
Total GST Percentage | 18 |
HSN Number | 85362010 |
Country of origin | Germany (DE) - Imported by ABB India Limited |