SKU: 600ELR
Categories: Meters, Relays, Timers, Counters, APFC
Measuring Parameter | Monitors True RMS Earth Leakage Current (upto 500mA) |
Electrical Connection | 1Ø-2W, 3Ø-4W, 3Ø-3W |
Supply Voltage | 230VAC ± 15% |
Trip Leakage current range | 30mA - 500mA, (30mA, 100mA, 300mA, 500mA) |
Trip time delay | 0, 2, 4, 6, 8, 10 sec (NA for 30mA range) |
Response time | Variable time settings (0, 2, 4, 6, 8, 10 sec), For 100mA, 300mA & 500mA current setting, (For 1x1n) & <30ms for 5xIn, For 0 sec trip setting for 100mA,300mA & 500mA, trip time will be less than <150ms, For 30mA : - <30ms (For 5xln) & <150ms (For 1xIn) |
CBCT Detection | Yes, when CBCT absent or short |
Accuracy | Current : 5% of In, Time : 5% of Set time |
Output Contact | 1 SPDT relay |
Output Rating | NO : 5A @ 250VAC NC: 3A @ 250VAC 5A @ 24V DC |
Size | 17.5 X 90 mm |
Mounting Type | DIN rail Mount |