0 0
0
No products in the quote.

1Ø Digital Pump Protection Relay

Brand: Selec

Product: PPRD-4M-1-230V
 
  • Monitors: Phase loss, Phase unbalance, Phase sequence, Overload trip current, Under / Over current and voltage in 1Ø pumps.
  • Auto / Remote test available.
  • Output contact : 1 C/O SPST relay
  • Direct 30A Relay output.
  • Aux Supply : 180 to 300V AC (L-N)
(Available)
Quantity

SKU: PPRD-4M-1-230V

Categories: Meters, Relays, Timers, Counters, APFC

Measuring ParameterMonitors Dry/Under Current, Over Current, Locked Current, Over Voltage, Under Voltage, Phase Failure and Overload
Electrical Connection1Ø - 2
Test / ResetManual / Auto reset
LED IndicationPower ON, Trip indication
DisplayPower 3 Digits, 7 Segment LED display
Voltage Measuring Range180 to 300V AC (L - N)
Power Consumption180 40VA (max)
Motor Rated Current Measuring range1A to 30A
Output ContactControl Output 1 NO Relay,
Relay Rating 32A@277V AC

Accuracy
Current Accuracy ±5% of rated current,
Voltage Accuracy ±1% of 300V,
Time Accuracy ±5% ±100msec



Functional Specifications
Over load NEMA class 5, 10, 15, 20, 30,
Over current ranges [Ir (Rated current) + 1 to 32A],
Under current [0.2A to Ir (Rated current) - 1],
Locked current / Stall current [Ir (Rated current) + 1 to 32A],
Over voltage 180V - 300V AC ( L - N ),
Under voltage 180V - 300V AC ( L - N )


Time Setting
Power ON delay 1sec (Fixed),
Trip time delay (Current & Voltage parameters) 0 - 999sec Recovery time (Current & Voltage parameters) 1 - 999sec,
Reset attempts 3 (fixed),
Reset Attempt Time Frame 1 - 999 mins
Auto Restart Attempts3 (Fixed)
MountingDIN Rail Mount
Size66.50 x 70 x 90 (H x W x L)

PRODUCT VARIANTS

Product Code
PPRD-4M-1-230V

0.00

5 Star
0%
4 Star
0%
3 Star
0%
2 Star
0%
1 Star
0%

Submit Your Review

Please login to write review!

Upload photos
You can upload up to 6 photos, each photo maximum size is 2048 kilobytes
PPRD-4M-1_Datasheet.pdf 29-03-2024 678.53 KB
PPRD-4M-1_Instruction_Manual.pdf 29-03-2024 189.84 KB

Related products